VT-MIPM 135 Series Specifications

by | Oct 26, 2019 | Product Specifications-Group

VT-MIPM-135-FDS, VT-MIPM-135-ADR, VT-MIPM-135-SPA, VT-MIPM-135-FFR

Product Applications:

  • Automatic Demand Response
  • Solar Tracker Controller
  • Fast Frequency Response

Industrial powerPC (32 bit data bus)

  • Operating system embedded Linux
  • Dynamic memory (RAM) 32 Mbytes – 32bit, 0 wait states
  • Program memory (Flash) 64 Mbytes
  • Retained memory (RAM) 512K (battery-backed)
  • Real-time clock battery-backed for time stamping and other operations
  • I/O Expansion RS-485 or Ethernet
  • Data logging
  • IEC 61131 programming
  • High Level C programming

ETHERNET PORT

  • 10/100BaseTx (auto-detecting)
  • RJ45 connection (auto-crossover)
  • Protocols TCP / IP, ARP, UDP, ICMP, DHCP, Modbus / TCP, optionally PPP, DNP3, IEC60870-5-101/104 and more

SERIAL PORT

  • Up to 115,200 baud
  • RS485 port A screws (485+, 485-, GND) 2-wire half-duplex
  • RS232 Port B RJ45 (TD, RD, CTS, RTS, CD, DTR,DSR, GND)
  • RS-232 Port D Screws (TD, RD, GND)
  • Protocols (master & slave) Modbus RTU/ASCII, Optional DNP3 slave,  IEC60870-5-101/104.

DISCRETE INPUTS

  • 12 channels (sinking or sourcing) for manual input and force load shed
  • Guaranteed ON voltage 9 VDC
  • Maximum voltage 30 VDC
  • Guaranteed OFF voltage & current 5.0 VDC & 1.5 mA DC
  • Input resistance 10K Ohms and 3 mA @ 24 VDC
  • Input current @ 24 VDC 3 mA
  • Filtered ON/OFF delay 25 mS (20 Hz max. counting) for contact bounce filtering
  • Fast ON/OFF delay 4 mS (100 Hz max. counting)
  • Count rate (see above) (10 KHz on channel 1 only)
  • Counter modes pulse, rate and run time
  • Poll time (all channels) 5 mS to 20 mS configuration dependent

DISCRETE OUTPUTS

  • 8 channels (10-30 VDC) 3 for Event Load Shed, 1 used for Off Line Indication (Open ADR only) 4 configurable spares
  • Min. and max. output load 1 mA to 1 Amp sourcing per channel
  • Max. OFF state leakage 0.05 mA
  • Inrush current 5 Amps (100 mS surge)
  • Typical ON characteristics 0.3 Ohms resistance and 0.3 VDC voltage drop @ 1A
  • Poll time (all channels) 5 mS to 20 mS configuration dependent

 

GRIDlinkArtTermLED

ANALOG

  • 6 Input channels (Full scale range 4-20 mA)
  • A/D resolution 16 bits (0.003%)
  • Full scale accuracy +/-0.1% (@20°C)
  • Span and offset temp. coef. +/-50 ppm per °C
  • Input impedance 100 Ohm (current range), 80 K Ohm voltage
  • Current protection Self-resetting fuses
  • DMRR (differential mode rejection) 66 dB at 50/60 Hz
  • CMRR (common mode rejection) Not applicable since analog inputs are single ended.
  • Fastest update time 50 mS (both channels) – configurable for longer integration times for better noise filtering

ENVIRONMENTAL

  • Input power 10-30 VDC
  • Input current 100 mA @ 24 VDC (typical)
  • Temperature -40 to 70°C (-40 to 85°C storage)
  • Humidity 5% to 95% RH (non-condensing)
  • Flammability UL 94V-0 materials
  • Electrical safety UL 508, CSA C22.2/14; EN610101; (IEC1010)
  • EMI emissions FCC part 15, ICES-003, Class A; EN55022; EN61326-1
  • EMC immunity EN61326-1 (EN61000-4-2,3,4,6)
  • Surge withstand IEEE-472 (ANSI C37.90)
  • Vibration IEC68-2-6
  • Hazardous locations (Class 1, Div 2, Groups A,B,C,D) UL 1604, CSA C22.2/213, Cenelec EN50021 Zone 2
  • Tested to Marine/offshore standards